Gammapilot FMG50 Commissioning
Endress+Hauser 73
Please note the following if using the linearization module with linearization tables
recorded semi-automatically:
The module assumes pulse rates are normalized and automatically switches the
internal measurement calculation to normalized values if the module is used. This
falsifies the assignment between the output value and the measured value. If the
linearization module has been opened with semi-automatic linearization curves, the
table mode must be set to "semi-automatic" again.
Note: the linearization can calculate an incorrect value if the wrong table mode is
used. The current output will also output an incorrect measured value in this case.
The following message is displayed following a successful calibration:
A0042225
The settings for the current output are made after the calibration of the operating mode in
the "Output settings" step
Settings of the current output
1. Set the lower limit value (4 mA) and the upper limit value (20 mA) of the current
output to the desired values of the primary measured value
A0042226
These values can be used for a zoom function or to invert the measured value to
the current value.
2. The control range of the current output can be modified
A0042227
The measuring range of the current output can be defined as: