Commissioning Gammapilot FMG50
78 Endress+Hauser
Configuring RSG45
Setting or deleting the limit values
1. Navigate to limit values: "Setup -> Extended setup -> Application -> Limit values"
2. Enter the limit values
FMG50 (density measurement), channel 1
Cnts_density_min: Pulse rate (pulses per second, cnt/s) of the FMG50 (density) at
atmospheric conditions (environment)
Atmos Density: atmospheric density (environment)
Cnts_density_max: pulse rate (pulses per second, cnt/s) of the FMG50 (density) at
maximum process density
max_Pro_density: maximum process density
FMG50 (level measurement), channel 2
Cnts_Level_empty: pulse rate (pulses per second, cnt/s) at 0 % level
Cnts_Level_full: pulse rate (pulses per second, cnt/s) at 100 % level
Pressure measurement, channel 3
Atmos Pressure: atmospheric pressure (reference)
Temperature measurement, channel 4
Atmos Temp: atmosphere temperature (reference)
Setting mathematical functions and linearization table
Display as percentage
1. In the Expert menu, navigate to the linearization table: Expert → Application →
Mathematics → Level → Linearization