Commissioning Gammapilot M FMG60 PROFIBUS PA
34 Endress+Hauser
Options/display:
• Stand alone: This option is selected if the Gammapilot M is used as a single, standalone
device.
• Master: This option is selected if the Gammapilot M is located at the beginning of a cascade
chain. It then receives the pulses from a connected slave, adds its own pulses and calculates
the measured value from this total.
• Slave: This option is selected if the Gammapilot M is located in the middle of a cascade
chain. It then receives the pulses from another connected slave or end slave, adds its own
pulses and transmits this total to the next device (master or slave). The calibration is
finished if this option is selected. If several transmitters are cascaded, the rest of the
calibration procedure is performed on the master only.
• End slave: This option is selected if the Gammapilot is located at the end of a cascade chain.
It does not receive pulses from another device but transmits its own pulses to the next
device (master or slave). The calibration is finished if this option is selected. If several
transmitters are cascaded, the rest of the calibration procedure is performed on the master
only.
• Not defined: Is displayed if the operating mode has not yet been selected. An option must
be selected in order to continue with the basic setup.
If a "slave" or an "end slave" is connected to "FieldCare", the pulse rate of this device is displayed
in the header instead of the measured value.
6.4.5 "Measurement mode" (*05)
Local display
Measurement mode *05
✓ Level
Switch
Density
This function is used to select the desired measurement mode.
Further options:
• Level measurement (continuous)
• Point level detection
• Density measurement (with temperature compensation if required)
• Concentration measurement (density measurement followed by linearization)
The operating mode can only be selected once. After this, the function is automatically
locked and can only be unlocked by resetting the Gammapilot M ("Reset" (*A3) function).