Commissioning Gammapilot M FMG60 PROFIBUS PA
52 Endress+Hauser
6.6.3 Calibration points
The following excerpt from the operating menu illustrates the procedure for entering the
density calibration points. The individual functions are explained in detail in the sections that
follow. The functions are only accessible once the background calibration has been performed.
*15
calibration
0: stop / edit
1: start
*11
avg. pulse
rate
*1C
density value
*1A
calibration point
1...9: cal. points for
various densities
10: recalibration point
1
*1D
cal. point
0: not used
1: used
2: clear
*1E
absorp.
coeff.
*1F
ref. pulse
rate
*19
next point
0: no
1: yes
Group
selection
E
0
*1B
density
calibration
-1: not
calibrated
A0037163-EN