Gammapilot M FMG60 with FOUNDATION Fieldbus Operation
Endress+Hauser 49
5.6.7 Diagnostic block
Operation
The Diagnostic block contains the error messages of the device. These parameters can also be read
out and edited using the VU331 display module.
The Diagnostic block is opened by clicking the "diagnostic" line.
Parameter changes from the tool are made off-line while the device is operating. The changes are
downloaded by first setting MODE_BLK = OOS then pressing the WRITE CHANGES button. If you
want to check all the values saved in the device, click READ ALL. To return to operation, set the
MODE_BLK to AUTO
7)
.
Block administration parameters
Instrument specific parameters
E+H_GAMMAPILOT_M_XXXXXXXX
TRANSDUCER_XXXXXX (TB)
DIAGNOSTIC_XXXXXX (DIAG)
DISPLAY_XXXXXX (DISP)
7) If MODE_BLK refuses to be changed to AUTO, an error is present. Control all parameters, perform the required changes and try again to change MODE_BLK
to AUTO.
Parameter Description
MODE_BLK See description in Resource block. The possible operating modes of the Transducer block
are:
AUTO: the block is operating as normal
OOS: the block is out of service.
TAG_DESC User description of the intended application of the block.
BLOCK_ERROR Shows the error status in conjunction with the block components.
Out-of-service: the block is in OOS mode
Parameter Position
Indicator
rel.
Index
Variable Name Size
[bytes]
Type Read Write Storage
Class
present error *A0 13 ACTUALERROR 2 UNSIGNED16 X dynamic
previous error *A1 14 LASTERROR 2 UNSIGNED16 X non-vol.
Clear last error *A2 15 CLEARLASTERROR 1 ENUM8 X X dynamic
Reset *A3 16 RESET 2 UNSIGNED16 X X dynamic
Unlock parameter *A4 17 OPERATIONCODE 2 UNSIGNED16 X X non-vol.
protocol+sw-no. *C2 18 PROSOFTVERSIONSTRING 16 VISIBLE STRING X constant