Gammapilot M FMG60 with FOUNDATION Fieldbus Operation
Endress+Hauser 51
5.6.9 Analog Input block
The Analog Input block processes the signal output by the Transducer block and forwards it to the
PLC or other function blocks.
L00-FMR2xxxx-05-00-00-en-008
Operation
The Analog Input block is opened by clicking the "Analog_Input" line.
Parameter changes from the tool are made off-line while the device is operating. The changes are
downloaded by first setting MODE_BLK = OOS then pressing the WRITE CHANGES button. If you
want to check all the values saved in the device, click READ ALL. Operation normally resumes as
soon as MODE_BLK is set to AUTO.
Block administration parameters
E+H_Gammapilot_M_XXXXXXXX
RESOURCE_XXXXXX (RB2)
TRANSDUCER_XXXXXX (TBUL)
ANALOG_INPUT_1_XXXXXX (AI)
Parameter Description
MODE_BLK See description in Resource block. The possible operating modes of the Transducer block
are:
– AUTO: the block is operating as normal
– MAN: the block is operated with a manually entered primary value.
– OOS: the block is out of service.
TAG_DESC User description of the intended application of the block.
BLOCK_ERROR Shows the error status in conjunction with the block components.
– Out-of-service: the block is in OOS mode
– Simulation active: shows the setting of DIP-switch SIM. Input error/process variable
with BAD status.
– configuration error