Commissioning Gammapilot M FMG60 with FOUNDATION Fieldbus
58 Endress+Hauser
6.1.1 Basic setup
Step Function Entry or selection Comments See section
1 Present date (*01) e.g.
12.11.04 10:30
Set day with O and S ;
Confirm with F;
The same applies for month, year,
hour and minute
6.3.1
2 Radiation source (*03) •
137
Cs
•
60
Co
• no compensation
Select with O and S;
Confirm with F
6.3.2
3 Master slave mode (*04) •Stand alone
•Master
•Slave
•End-slave
•not defined
Select with O and S;
Confirm with F
6.3.3
4 Measurement mode (*05) • level
• limit
•density
• concentration
Select with O and S;
Confirm with F
6.3.4
The following functions for density and concentration measurements only:
5 Density unit (*06) •g/cm
3
•g/l
•...
Select with O and S;
Confirm with F
6.3.5
6 Min. density (*07)
(lower limit of the
measuring range)
e.g.
0.9500 g/cm
3
Set each decimal place with O and S
and confirm with F;
After the last place: confirm the
whole value with F.
6.3.6
7 Max. density (*08)
(upper limit of the
measuring range)
e.g.
1.2500 g/cm
3
Set each decimal place with O and S
and confirm with F;
After the last place: confirm the
whole value with F.
6.3.7
8 Pipe diameter unit (*09) •mm
•inch
Select with O and S;
Confirm with F
6.3.8
9 Pipe diameter (*0A) e.g.
200 mm
Set each decimal place with O and S
and confirm with F;
After the last place: confirm the
whole value with F.
6.3.9
The following function for all measurement methods:
10 Output damping (*0B) e.g. 60 s Set each decimal place with O and S
and confirm with F;
After the last place: confirm the
whole value with F.
6.3.10