Micropilot S FMR533 4 to 20 mA HART Wiring
Endress+Hauser 27
4.3 Recommended connection
4.3.1 Equipotential bonding
Connect the Equipotential bonding to the external ground terminal of the transmitter.
4.3.2 Wiring screened cable
"
Caution!
In Ex applications, the device must only be grounded on the sensor side. Further safety instructions
are given in the separate documentation for applications in explosion hazardous areas.
4.4 Degree of protection
housing: IP68, NEMA 6P (open housing and removed liquid crystal display: IP20, NEMA 1)
antenna: IP68 (NEMA 6P)
4.5 Post-connection check
After wiring the measuring device, perform the following checks:
Is the terminal allocation correct ( ä 22)?
Is the cable gland tight?
Is the housing cover screwed tight?
If auxiliary power is available:
Is the device ready for operation and does the liquid crystal display show any value?
Is grounding (tank potential) correct?