Micropilot S FMR533 4 to 20 mA HART Commissioning
Endress+Hauser 41
6.3 Basic Setup
L00-FMR533xx-19-00-00-en-001
SD
F
L
D
BD
E
flange:
reference point of
measurement
E = empty calibr. (= zero)
settings in 005 settings in 006
D = distance (distance flange / product) L
display in 0A5 in 0A6
F = full calibr. (= span)
= level
display
SD = safety settings BD = blocking dist.
settings in 015 settings in 059
Distance
correct
Meas. value
correct
Distance
incorrect
Meas. value
incorrect
...
(description see BA00217F/00/EN)
measuring cond.
process cond.
pipe diameter
dist. / meas.
value
start mapping
According to
envelope curve
According to
hand dipping
history reset
adjust
empty calibr.ā€žā€œ
Check distance
Range of mapping
empty calibr.
full calibr.
basic setup (standard)
option
first point corrects
further points correct linearity
offset
Commissioning
(for bypass/stilling well)
flat ceiling