Micropilot S FMR533 4 to 20 mA HART Commissioning
Endress+Hauser 47
Function "pipe diameter" (007)
This function is used to enter the pipe diameter of the stilling well or bypass pipe.
L00-FMR2xxxx-14-00-00-de-011
Microwaves propagate slower in pipes than in free space. This effect depends on the inside diameter
of the pipe and is automatically taken into account by the Micropilot. It is only necessary to enter
the pipe diameter for applications in a bypass or stilling well.
Display "dist./ meas. value" (008)
The distance measured from the reference point to the product surface and the level calculated
with the aid of the empty adjustment are displayed. Check whether the values correspond to the
actual level or the actual distance. The following cases can occur:
Distance correct – level correct È continue with the next function, "check distance" (051)
Distance correct – level incorrect È Check "empty calibr" (005)
Distance incorrect – level incorrect È continue with the next function, "check distance" (051)