Trouble-shooting Micropilot S FMR533 4 to 20 mA HART
72 Endress+Hauser
9.3 Application errors
Error Output Possible cause Remedy
A warning or alarm
has occurred
Depending on the configuration See table of
error messages
( ä 70)
1. See table of error messages
( ä 70)
Measured value
(00) is incorrect
L00-FMR53xxx-19-00-00-en-007
Measured distance
(008) OK?
yes
1. Check empty calibr. (005) and
full calibr (006).
2. Check linearisation:
level/ullage (040)
max. scale (046)
diameter vessel (047)
Check table
3. Check dip table
no
Measurement in bypass
or stilling well?
yes
1. Is bypass or stilling well
selected in tank shape?
2. Is the pipe diameter
(007) correct?
3. Pipe diameter correction (032 )
activated?
no
Is "offset" (057) active? yes
1. offset (057) correctly set?
no
An interference echo
may have been
evaluated.
yes
1. Carry out tank mapping
basic setup
2. Activate auto correction (031)
No change off
measured value on
filling/emptying
L00-FMR53xxx-19-00-00-en-006
Interference echo from
installations, nozzle or
extension on the
antenna
1. Carry out tank mapping
basic setup
2. If necessary, clean antenna
3. If necessary, select better
mounting position ( ä 11)
20 mA/100%
F m/ft
E m/ft
4 mA/0% t
D m/ft (008)
actual
expected
20 mA/100%
4 mA/0% t
actual
expected