Proline t-mass I 300 HART Technical data
Endress+Hauser 169
15.4 Output
Output signal Current output 4 to 20 mA HART
Order code "Output; input 1" (20):
Option BA: current output 4 to 20 mA HART
Signal mode Can be set to:
Active
Passive
Current range Can be set to:
4 to 20 mA NAMUR
4 to 20 mA US
4 to 20 mA
0 to 20 mA (only if the signal mode is active)
Fixed current
Open-circuit voltage DC 28.8 V (active)
Maximum input voltage DC 30 V (passive)
Load 250 to 700 Ω
Resolution 0.38 µA
Damping Configurable: 0 to 999.9 s
Assignable measured
variables
Mass flow
Volume flow
Corrected volume flow
FAD volume flow
Flow velocity
Temperature
Energy flow
Pressure
Density
Heat flow
Electronics temperature
2nd temperature heat difference
For SIL (application package), only mass flow
Current output 4 to 20 mA HART Ex i
Order code "Output; input 1" (20) choose from:
Option CA: current output 4 to 20 mA HART Ex i passive
Option CC: current output 4 to 20 mA HART Ex i active
Signal mode Depends on the selected order version.
Current range Can be set to:
4 to 20 mA NAMUR
4 to 20 mA US
4 to 20 mA
0 to 20 mA (only if the signal mode is active)
Fixed current
Open-circuit voltage DC 21.8 V (active)
Maximum input voltage DC 30 V (passive)
Load 250 to 400 Ω (active)
250 to 700 Ω (passive)
Resolution 0.38 µA