Operating menu and parameter description iTEMP TMT142B
84 Endress+Hauser
Factory setting EH_TMT142B_serial number
Locking status
Navigation System → Device management → Locking status
Description Displays the device locking status. When write protection is activated, write access to the
parameters is disabled.
User interface Enabled or disabled check box: Locked by hardware
Device reset
Navigation System → Device management → Device reset
Description Use this function to reset the device configuration - either entirely or in part - to a defined
state.
Options Not active
No action is executed and the user exits the parameter.
To factory defaults
All the parameters are reset to the factory setting.
To delivery settings
All parameters are reset to the order configuration. The order configuration can differ
from the factory setting if customer-specific parameter values were defined when the
device was ordered.
Restart device
The device is restarted but the device configuration remains unchanged.
Factory setting Not active
Configuration counter
Navigation System → Device management → Configuration counter
Description Displays the counter reading for changes to device parameters.
Static parameters, whose values change during optimization or configuration, cause
this parameter to increment by 1. This supports parameter version management. If
several parameters change, e.g. as a result of loading parameters from FieldCare etc.
to the device, the counter can show a higher value. The counter cannot be reset and is
also not reset to the default value when the device is reset. If the counter value
exceeds 65535, it starts again at 1.