TMT162
20 Endress+Hauser
This ordering information can give an overview about the available order options. Your local Endress+Hauser
sales organization can provide detailed information in addition.
Marking:
5 Pt1000 (-200 to 250 °C, -328 to 482 °F, min. span 10 K, 18 °F)
6 Ni1000 (-60 to 150 °C, -76 to 302 °F, min. span 10 K, 18 °F)
7 Resistance transmitter (10 to 400 Ω, min. span 10 Ω)
8 Resistance transmitter (10 to 2000 Ω, min. span 100 Ω)
B Type B (0 to 1820 °C, 32 to 3308 °F, min. span 500 K, 900 °F)
C Type C (0 to 2320 °C, 32 to 4208 °F, min. span 500 K, 900 °F)
D Type D (0 to 2495 °C, 32 to 4523 °F, min. span 500 K, 900 °F)
E Type E (-270 to 1000 °C, -454 to 1832 °F, min. span 50 K, 90 °F)
F Cu10 (-100 to 260 °C, -148 to 500 °F, min. span 10 K, 18 °F, Edison Copper Winding No.
15, a = 0.004274)
G Pt100 (-100 to 700 °C, -148 to 1292 °F, min. span 10 K, 18 °F)
H Ni120 (-70 to 270 °C, -94 to 518 °F, min. span 50 K, 90 °F)
J Type J (-210 to 1200 °C, -346 to 2192 °F, min. span 50 K, 90 °F)
K Type K (-270 to 1372 °C, -454 to 2501 °F, min. span 50 K, 90 °F)
L Type L (-200 to 900 °C, -328 to 1652 °F, min. span 50 K, 90 °F)
M Pt50 (-200 to 1100 °C, -328 to 2012 °F, min. span 10 K, 18 °F, GOST, a = 0.003911)
N Type N (-270 to 1300 °C, -454 to 2372 °F, min. span 50 K, 90 °F)
P Pt100 (-200 to 850 °C, -328 to 1562 °F, min. span 10 K, 18 °F, GOST, a = 0.003911)
Q Cu50 (-200 to 200 °C, -328 to 392 °F, min. span 10 K, 18 °F, GOST, a = 0.004278)
R Type R (-50 to 1768 °C, -58 to 2314.4 °F, min. span 500 K, 900 °F)
S Type S (-50 to 1768 °C, -58 to 2314.4 °F, min. span 500 K, 900 °F)
T Type T (-270 to 400 °C, -454 to 752 °F, min. span 50 K, 90 °F)
U Type U (-200 to 600 °C, -328 to 1112 °F, min. span 50 K, 90 °F)
V Voltage transmitter (-20 to 100 mV, min. span 5 mV)
Y Special, to be specified
Communication; Configuration:
A HART; Factory setup Pt100/3-wire/0-100 °C, NAMUR NE43, SIL
B HART; Measuring range, see additional spec., NAMUR NE43, SIL
C HART; TC config. range, see questionnaire, NAMUR NE43, SIL
D HART; RTD config. range, see questionnaire, NAMUR NE43, SIL
E PROFIBUS PA; see additional specification
K FOUNDATION Fieldbus; Factory setup Pt100/3-wire
Additional Option:
A 50Hz line voltage filter
B Works calib.certif.,6-point
1)
, 50Hz filter
1) The factory calibration certificate is an evaluation and documentation of 6 fixed resistance values over the complete
measuring range.
C LR, ABS marine certificate, 50Hz filter
D Factory calibration certificate 6-point
1)
+LR, ABS, 50Hz filter, marine certificate
K 60Hz line voltage filter
Sensor:
A 1x input, HART
B 2x input, PV = sensor 1, Sensor2 not active
C 2x input, PV = difference
D 2x input, PV = average
E 2x input, sensor back up
TMT162- Order code (complete)
51003528 TAG print/configuration 2 x 16 characters
51003546 Descriptor print/configuration 16 characters (only HART
®
device)
51002393 Label metal (TAG)
51010487 Label paper 3 x 16 characters (TAG)
51002392 Configuration bus address
Configuration Sensor Type: