Breakdown information
Load (HART
®
)
Linearization/transmission
behavior
Temperature linear, resistance linear, voltage linear
Filter 1st order digital filter: 0 to 60 s
Current consumption
HART
®
Breakdown information to NAMUR NE43:
The information is created when the measuring information is invalid or not present anymore and gives a complete listing
of all errors occurring in the measuring system.
Under ranging Standard linear drop to 3.8
Over ranging Standard linear rise to 20.5
Failure, e. g. sensor break; sensor short
circuit
To NAMUR NE43 ≤ 3.6 mA ("low") or ≥ 21 mA ("high")
can be selected
1)
1) The high alarm is adjustable between 21.6 mA and 23 mA allowing for flexibility when working with the
requirements of most control systems.
FOUNDATION Fieldbus™
Status message according to specification FOUNDATION Fieldbus™.
PROFIBUS
®
PA
Status and alarms according to specification PROFIBUS
®
PA Profile 3.01
R
b max.
= (U
b max.
- 11 V) / 0.022 A (current output)
a0010971-en
U
b
40 V
1318
1068
250
11 V
0
34.5 V16.5 V
Supply voltage (V DC)
HART-
operational
region
Load ( )W
HART
®
Current consumption 3.6 mA to 22 mA
Min. current consumption ≤ 3.5 mA
Current limit ≤ 23 mA
FOUNDATION Fieldbus™
Current consumption (device basic current) ≤ 12 mA
Switch-on current (device inrush current) ≤ 12 mA
Error current FDE (Fault Disconnection
Electronic)
0 mA
PROFIBUS
®
PA
Current consumption (device basic current) ≤ 11 mA
Error current FDE (Fault Disconnection
Electronic)
0 mA