Commissioning iTEMP TMT162
22 Endress+Hauser
6.2 Access to the operating menu via the operating tool
The transmitter and measured value display are configured via the HART
®
protocol or CDI (=
Endress+Hauser Common Data Interface). The following operating tools are available for this
purpose:
Operating tools
FieldCare, DeviceCare, Field Xpert
(Endress+Hauser)
SIMATIC PDM
(Siemens)
AMS Device Manager
(Emerson Process Management)
Field Communicator 475
(Emerson Process Management)
The configuration of device-specific parameters is described in detail in the Operating
Instructions for the device.
7 Commissioning
7.1 Post-installation check
Before commissioning the measuring point, make sure that all final checks have been carried
out:
• "Post-mounting check" checklist
• "Post-connection check" checklist
7.2 Switching on the device
Once you have completed the post-connection checks, switch on the supply voltage. The
transmitter performs a number of internal test functions after power-up. During this process,
a sequence containing device information appears on the display.
Step Display
1 Text "Display" and firmware version of the display
2 Firm logo
3 Device name (scrolling text)
4 Firmware, hardware revision, device revision and device address
5 For devices in SIL mode: SIL-CRC is displayed
6a Current measured value or
6b Current status message
If the switch-on procedure is not successful, the relevant diagnostic event is displayed, depending on the
cause. A detailed list of diagnostic events and the corresponding troubleshooting instructions can be
found in the Operating Instructions.