iTEMP TMT162 Diagnostics and troubleshooting
Endress+Hauser 37
Diagnostic event and event text
The fault can be identified by means of the diagnostic event. The event text helps you by
providing information on the fault.
Diagnostic event
Status signal Event number Event text
Example F 042 Sensor corroded
3-digit number
If two or more diagnostic events are pending simultaneously, only the diagnostic message
with the highest priority is shown. Additional pending diagnostic messages are shown in
the Diagnostic list submenu →  85
. The status signal dictates the priority in which
the diagnostic messages are displayed. The following order of priority applies: F, C, S, M. If
two or more diagnostic events with the same status signal are active simultaneously, the
numerical order of the event number dictates the order of priority in which the events are
displayed, e.g.: F042 appears before F044 and before S044.
Past diagnostic messages that are no longer pending are shown in the Event logbook
submenu→  86.
9.2.2
Overview of diagnostic events
Each diagnostic event is assigned a certain event behavior at the factory. The user can
change this assignment for certain diagnostic events.
Example:
Settings Device behavior
Configuration examples Diagnostic
number
Status
signal
Diagnostic
behavior from
the factory
Status signal
(output via HART®
communication)
Current
output
PV, status Display
1. Default setting 047 S Warning S Measured
value
Measured value,
UNCERTAIN
S047
2. Manual setting: status
signal S changed to F
047 F Warning F Measured
value
Measured value,
UNCERTAIN
F047
3. Manual setting: Warning
diagnostic behavior changed
to Alarm
047 S Alarm S Configured
error current
Measured value,
BAD
S047
4. Manual setting: Warning
changed to Disabled
047 S
1)
Disabled -
2)
Last valid
measured
value
3)
Last valid
measured value,
GOOD
S047
1) Setting is not relevant.
2) Status signal is not displayed.
3) The error current is output if no valid measured value is available.
The relevant sensor input for these diagnostic events can be identified with the
Actual diag channel parameter or on the display.