Technische Daten iTEMP TMT162
52 Endress+Hauser
Standard Designation Measuring range Measured error (±)
Resistance
transmitter
Resistance Ω 10 to 400 Ω 33 mΩ ME = ± (21 mΩ + 0.003% *
(MV - LRV))
0.03 % (
4.8 µA)
10 to 2 000 Ω 235 mΩ ME = ± (
35 mΩ + 0.010% *
(MV - LRV))
1)
Measured value transmitted via HART
®
.
2) Percentages based on the configured span of the analog output signal.
3) Maximum measured error for the specified measuring range.
4) Deviations from maximum measured error due to rounding is possible.
Measured error for thermocouples (TC) and voltage transmitters
Standard Designation Measuring range Measured error (±)
Digital
1)
D/A
2)
Maximum
3)
Based on measured value
4)
IEC 60584-1
Type A (30) 0 to +2 500 °C (+32 to +4
532 °F) ≤ 1.25 °C (2.25 °F)
ME = ± (0.08 °C (0.14 °F) +
0.018% * (MV - LRV))
0.03 % (
4.8 µA)
Type B (31)
+500 to +1 820 °C
(+932 to +3 308 °F)
≤ 1.23 °C (2.21 °F)
ME = ± (1.23 °C (2.14 °F) -
0.05% * (MV - LRV))
IEC 60584-1 / ASTM
E988-96
Type C (32)
0 to +2 000 °C (+32 to +3 632 °F)
≤ 0.6 °C (1.08 °F)
ME = ± (0.5 °C (0.9 °F) +
0.005% * MV - LRV))
ASTM E988-96 Type D (33) ≤ 0.63 °C (1.13 °F)
ME = ± (0.63 °C (1.13 °F) -
0.007% * MV - LRV))
IEC 60584-1
Type E (34)
–150 to +1 000 °C
(–238 to +1 832 °F)
≤ 0.19 °C (0.34 °F)
ME = ± (0.19 °C (0.3 °F) -
0.006% * (MV - LRV))
Type J (35)
–150 to +1 200 °C
(–238 to +2 192 °F)
≤ 0.23 °C (0.41 °F)
ME = ± (0.23 °C (0.4 °F) -
0.005% * (MV - LRV))
Type K (36) ≤ 0.30 °C (0.54 °F)
ME = ± (0.3 °C (0.5 °F) -
0.002% * (MV - LRV))
Type N (37)
–150 to +1 300 °C
(–238 to +2 372 °F)
≤ 0.40 °C (0.72 °F)
ME = ± (0.4 °C (0.7 °F) -
0.01% * (MV - LRV))
Type R (38)
+50 to +1 768 °C
(+122 to +3 214 °F)
≤ 0.95 °C (1.71 °F)
ME = ± (0.95 °C (1.7 °F) -
0.025% * (MV - LRV))
Type S (39) ≤ 0.98 °C (1.76 °F)
ME = ± (0.98 °C (1.8 °F) -
0.02% * (MV - LRV))
Type T (40) –150 to +400 °C (–238 to +752 °F) ≤ 0.31 °C (0.56 °F)
ME = ± (0.31 °C (0.56 °F) -
0.034% * (MV - LRV))
DIN 43710
Type L (41)
–150 to +900 °C
(–238 to +1 652 °F)
≤ 0.26 °C (0.47 °F)
ME = ± (0.26 °C (0.47 °F) -
0.008% * (MV - LRV))
Type U (42)
–150 to +600 °C
(–238 to +1 112 °F)
≤ 0.27 °C (0.49 °F)
ME = ± (0.27 °C (0.49 °F) -
0.022% * (MV - LRV))
GOST R8.8585-2001 Type L (43)
–200 to +800 °C
(–328 to +1 472
°F)
≤ 2.13 °C (3.83 °F)
ME = ± (2.13 °C (3.83 °F) -
0.012% * (MV - LRV))
Voltage transmitter
(mV)
–20 to +100 mV 8.9 µV ME = ± (6.5 µV + 0.002% *
(MV - LRV))
4.8 µA
1)
Measured value transmitted via HART
®
.
2) Percentages based on the configured span of the analog output signal.
3) Maximum measured error for the specified measuring range.
4) Deviations from maximum measured error due to rounding is possible.
MV = Measured value
LRV = Lower range value of relevant sensor

Table of Contents