iTEMP TMT162 Operating menu and parameter description
Endress+Hauser 73
14.1.1 "Advanced setup" submenu
Drift/difference mode
If two sensors are connected and the measured values differ by a specified value, a status
signal is generated as a diagnostic event. The drift/difference monitoring function can be
used to verify the correctness of the measured values and for mutual monitoring of the
connected sensors. Drift/difference monitoring is enabled with the Drift/difference mode
parameter. A distinction is made between two specific modes. If the In band option is
selected (ISV1-SV2I < drift/difference set point), a status message is issued if the value
drops below the set point, or if the value exceeds the set point if the Out band (drift)
option is selected (ISV1-SV2I > drift/difference set point).
Procedure for configuring the drift/difference mode
1. Start
ß
2. For drift/difference monitoring, select Out band for drift detection and In band for difference monitoring.
ß
3. Set the set point for drift/difference monitoring to the desired value.
ß
4. End
A0014782
19 Drift/difference mode
A Value under range
B
Value over range
D Drift
L+,
L-
Upper (+) or lower (-) set point
t Time
x Diagnostic event, status signal is generated
Enter access code
Navigation Setup → Advanced setup → Enter access code
Expert → Enter access code
Description Use this function to enable the service parameters via the operating tool. If an incorrect
access code is entered, the user retains his current access authorization.
If a value is entered that is not to equal to the access code, the parameter is
automatically set to 0. The service parameters should only be modified by the service
organization.