iTEMP TMT162 Operating menu and parameter description
Endress+Hauser 75
"Sensor" submenu
Sensor offset n
n = Stands for the number of sensor inputs (1 and 2)
Navigation Setup → Advanced setup → Sensor → Sensor offset n
Expert → Sensor → Sensor n → Sensor offset n
Description Use this function to set the zero point correction (offset) of the sensor measured value.
The value indicated is added to the measured value.
User entry -10.0 to +10.0
Factory setting 0.0
Drift/difference mode
Navigation Setup → Advanced setup → Sensor → Drift/difference mode
Expert → Sensor → Diagnostic settings → Drift/difference mode
Description Use this function to choose whether the device reacts to the drift/difference limit value
being exceeded or undershot.
Can only be selected for 2-channel operation.
Additional information If the Out band (drift) option is selected, a status signal is displayed if the absolute value
for the differential value exceeds the drift/difference set point
If the In band option is selected, a status signal is displayed if the absolute value for the
differential value drops below the drift/difference set point.
User entry Off
Out band (drift)
In band
Factory setting Off
Drift/difference alarm delay
Navigation Setup → Advanced setup → Sensor → Drift/difference alarm delay
Expert → Sensor → Diagnostic settings → Drift/difference alarm delay
Prerequisite The Drift/difference mode parameter must be activated with the Out band (drift) or In
band option. →  75