iTEMP TMT162 Operating menu and parameter description
Endress+Hauser 77
NOTICE
Current trimming does not affect the digital HART
®
value. This can cause the
measured value shown on the display to differ marginally from the value displayed in
the higher-level system.
‣
The digital measured values can be adapted with the sensor trimming parameter in the
menu Expert → Sensor → Sensor trimming.
Procedure
1. Start
ß
2. Install an accurate ammeter (more accurate than the transmitter) in the current loop.
ß
3. Switch on current output simulation and set the simulation value to 4 mA.
ß
4. Measure the loop current with the ammeter and make a note of the value.
ß
5. Set the simulation value to 20 mA.
ß
6. Measure the loop current with the ammeter and make a note of the value.
ß
7. Enter the current values determined as adjustment values in the Current trimming 4 mA / 20 mA
parameters
ß
8. End
Output current
Navigation Setup → Advanced setup → Current output→ Output current
Description Use this function to view the calculated output current in mA.
Failure mode
Navigation Setup → Advanced setup → Current output→ Failure mode
Expert → Output → Failure mode
Description Use this function to select the signal on alarm level of the current output in the event of an
error.
Additional information If Max.
is selected, the signal on alarm level is specified using the Failure current
parameter.
User entry • Min.
• Max.