iTEMP TMT162 Operating menu and parameter description
Endress+Hauser 83
Navigation Setup → Advanced setup → Administration → Device reset
Expert → System → Device reset
Description Use this function to reset the device configuration - either entirely or in part - to a defined
state.
User entry Not active
No action is executed and the user exits the parameter.
To factory defaults
All the parameters are reset to the factory setting.
To delivery settings
All parameters are reset to the order configuration. The order configuration can differ
from the factory setting if customer-specific parameter values were defined when the
device was ordered.
Restart device
The device is restarted but the device configuration remains unchanged.
Factory setting Not active
Define device write protection code
Navigation Setup → Advanced setup → Administration → Define device write protection code
Expert → System → Define device write protection code
Description Sets a write protection code for the device.
If the code is programmed into the device firmware it is saved in the device and the
operating tool displays the value 0 so that the defined write protection code is not
openly displayed for viewing.
User entry 0 to 9 999
Factory setting 0
If the device is delivered with this factory setting the device write protection is not
active.
Additional information Activating device write protection: To do so, enter a value in the Enter access code
parameter that does not correspond to the write protection code defined here.
Deactivating device write protection: If device write protection is activated, enter the
defined write protection code in the Enter access code parameter.
Once the device has been reset to the factory setting or the order configuration, the
defined write protection code is no longer valid. The code adopts the factory setting (=
0).
Hardware write protection (DIP switches) is active:
Hardware write protection has priority over the software write protection described
here.
No value can be entered in the Enter access code parameter. The parameter is a read
only parameter.
Device write protection via software can only be defined and activated if hardware
write protection via the DIP switches is disabled .→  23
If the write protection code has been forgotten, it can be deleted or overwritten by
the service organization.