Operating menu and parameter description iTEMP TMT162
90 Endress+Hauser
Display Measured value display ↔ C491 (current output simulation)
User entry Off
On
Factory setting Off
Additional information The simulation value is defined in the Value current output
parameter.
Value current output
Navigation Diagnostics → Simulation → Value current output
Expert → Diagnostics → Simulation → Value current output
Additional information The Current output simulation
parameter must be set to On.
Description Use this function to set a current value for the simulation. In this way, users can verify the
correct adjustment of the current output and the correct function of downstream switching
units.
User entry 3.59 to 23.0 mA
Factory setting 3.58 mA