iTEMP TMT162 Operating menu and parameter description
Endress+Hauser 97
Call./v. Dusen coeff. R0
Navigation Expert → Sensor → Sensor n → Linearization → Call./v. Dusen coeff. R0
Prerequisite: The RTD platinum (Callendar/Van Duse) option is enabled in the Sensor type parameter.
Description Use this function to set the R0 Value only for linearization with the Callendar/Van Dusen
polynomial.
User entry 40.000 to 1 050.000
Factory setting 100.000 Ohm
Call./v. Dusen coeff. A, B and C
Navigation Expert → Sensor → Sensor n → Linearization → Call./v. Dusen coeff. A, B, C
Prerequisite: The RTD platinum (Callendar/Van Duse) option is enabled in the Sensor type parameter.
Description Use this function to set the coefficients for sensor linearization based on the
Callendar/Van Dusen method.
Factory setting A: 3.910000e-003
B: -5.780000e-007
C: -4.180000e-012
Polynomial coeff. R0
Navigation Expert → Sensor → Sensor n → Linearization → Polynomial coeff. R0
Prerequisite: The RTD poly nickel or RTD copper polynomial option is enabled in the Sensor type
parameter.
Description Use this function to set the R0 Value only for linearization of nickel/copper sensors.
User entry 40.000 to 1 050.000 Ohm
Factory setting 100.00 Ohm
Polynomial coeff. A, B
Navigation Expert → Sensor → Sensor n → Linearization → Polynomial coeff. A, B