iTEMP TMT71, TMT72, TMT82, TMT84, TMT85 XA01007T
Endress+Hauser 13
Safety
instructions
Hazardous area
Zone 1, 2 or Zone 21, 22
Non-hazardous area
e.g RTD or TC Sensor
- mounted remote/integral
- optional 2 channels
Approved sensor
TMT8x
TMT7x
Local potential equalisation
DO NOT OPEN IN A POTENTIALLY
EXPLOSIVE ATMOSPHERE
See supply voltage of
assembled transmitter
A0016773-EN
Safety
instructions:
Installation
Type of protection flameproof
Comply with the installation and safety instructions in the Operating
Instructions.
Install the device according to the manufacturer's instructions and
any other valid standards and regulations (e.g. IEC/EN 60079-14).
The housing of the field transmitter must be connected to the
potential matching line.
Only the approved wire entries as specified in paragraph 10.3 of
IEC/EN 60079-14, paragraph 16 of IEC/EN 60079-0, paragraph 13
of IEC/EN 60079-1 must be used.
For connection through a conduit entry approved for this purpose the
associated sealing facility shall be mounted directly to the housing.
Seal unused entry glands with approved sealing plugs that correspond
to the type of protection.
For operating the field transmitter housing at an ambient
temperature under -20 °C, appropriate cables, cable entries and
sealing facilities permitted for this application must be used.
For ambient temperatures higher than +70 °C, use suitable heat-
resisting cables or wires, cable entries and sealing facilities for Ta +5
K above surrounding.
During operation, the cover must be screwed all the way in and the
cover's safety catch must be fastened.