EasyManua.ls Logo

Endress+Hauser iTEMP TMT82 - Connecting the Power Supply and Signal Cables

Endress+Hauser iTEMP TMT82
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
iTEMP TMT82 Wiring
Endress+Hauser 19
5.2.1 Connecting to spring terminals
A flat-bladed screwdriver, size 3 mm is required.
A B C D
A0008322
 10 Spring terminal connection
Pos. A, solid wire:
1. Strip wire end. Min. stripping length 10 mm (0.39 in).
2. Insert the wire end into the terminal (A).
3. Pull the wire gently to ensure it is connected correctly. Repeat from step 1 if
necessary.
Pos. B, fine-strand wire without ferrule:
1. Strip wire end. Min. stripping length 10 mm (0.39 in).
2. Operate lever opener with tool (B).
3. Insert the wire end into the terminal (B).
4. Release lever opener.
5. Pull the wire gently to ensure it is connected correctly. Repeat from step 1 if
necessary.
Pos. C and D, releasing the connection:
1. Operate lever opener with tool (C).
2. Remove wire from terminal (D).
3. Release lever opener.
When connecting flexible cables and spring terminals, it is not recommended to use
ferrules.
5.3 Connecting the power supply and signal cables
L
CAUTION
Switch off power supply before installing or connecting the transmitter. Failure to
observe this may result in destruction of parts of the electronics.
Cable specification
A normal device cable suffices if only the analog signal is used.
A shielded cable is recommended for HART
®
communication. Observe grounding
concept of the plant.
In the case of the DIN rail version, a shielded cable must be used if the sensor cable
length exceeds 30 m (98.4 ft). The use of shielded sensor cables is generally
recommended.

Table of Contents

Other manuals for Endress+Hauser iTEMP TMT82

Related product manuals