Wiring iTEMP TMT82
20 Endress+Hauser
Please also observe the general procedure on → 17.
*
*
1 2 3
4
2-
1+
2-
1+
*
2- 1+
5
6
7
4
5
7
A0017841
11 Connecting the signal cables and power supply
1 Head transmitter installed in field housing
2 Head transmitter installed in terminal head
3 DIN rail transmitter mounted on DIN rail
4
Terminals for HART
®
protocol and power supply
5 Internal ground connection
6 External ground connection
7
Shielded signal cable (recommended for HART
®
protocol)
• The terminals for connecting the signal cable (1+ and 2-) are protected against
reverse polarity.
• Conductor cross-section:
– Max. 2.5 mm
2
for screw terminals
– max. 1.5 mm
2
for spring terminals. Min. stripping length of cable
10 mm (0.39 in).
5.4 Shielding and grounding
The specifications of the HART FieldComm Group must be observed during installation.
A0014463
12
Shielding and grounding the signal cable at one end with HART
®
communication
1 Optional grounding of the field device, isolated from cable shielding
2 Grounding of the cable shield at one end
3 Supply unit
4
Grounding point for HART
®
communication cable shield