Operating menu and parameter description iTEMP TMT82
78 Endress+Hauser
Description Use this function to set the length of time the measured values are displayed if the values
alternate on the display. The display only alternates between values if more than one
measured value is defined.
• The Value 1 display - Value 3 display parameters are used to specify what
measured values are shown on the display → 78.
• The display format of the displayed measured values is specified using the
Format display parameter.
User input 4 to 20 s
Factory settings 4 s
Format display
Navigation Setup → Advanced setup → Display → Format display
Expert → System → Display → Format display
Description Use this function to select how the measured value is shown on the local display. The
display format Measured value or Measured value with bar graph can be configured.
Options: • Value only
• Value + Bargraph
Factory settings Value only
Additional information Value only
A0014564
Value + Bargraph
A0014563
Value 1 display