iTEMP TMT84 Commissioning
Endress+Hauser 19
A0041962
 11 Configuring the device address using the example of bus address 49
DIP switch set to ON: 32 + 16 + 1 = 49. Furthermore, SW/HW DIP switch set to "HW" and ADDR
ACTIVE to "ON".
6.2 Configuration of the head transmitter and PA functions
PROFIBUS® PA functions and device-specific parameters are configured via fieldbus
communication. The following configuration systems are available for this purpose:
Endress+Hauser FieldCare (DTM)
SIMATIC PDM (EDD)
The step-by-step procedure for commissioning the fieldbus functions for the first time is
described in detail in the comprehensive Operating Instructions, as is the configuration
of device-specific parameters.
7 Commissioning
7.1 Switching on the transmitter
Once you have successfully completed the final checks, it is time to switch on the supply
voltage. The transmitter performs a number of internal test functions after power-up. During
this process, a sequence containing device information appears on the display.
The device operates as normal after approx. 8 seconds, and the attached display after approx.
12 seconds! Normal measuring mode commences as soon as the switch-on procedure is
completed. Measured values and status values appear on the display.