11 Operation using PROFIBUS
®
PA TMT84
54 Endress + Hauser
11.2 Standard setup
The following parameter groups are available in the standard setup. These parameters are used for
basic device configuration. The head transmitter can be put into operation with this limited param-
eter set.
11.2.1 Group Display/Operation
The settings for displaying the measured value on the optional TID10 plug-in display are made in
the Display/Operation menu. The following parameters can be found in the Display/Operation
group and under Expert System Display.
!
Note!
These settings do not have any effect on the output values of the transmitter. They are only used to
configure how information is shown on the display.
Display/operation
Menu item Parameter
"Display/opera-
tion"
(Expert-
System
Display)
Name
Parame-
ter access
Description
Alternating time read/
write
Entry (in s) as to how long a value should be shown on the
display. Setting from 4 to 60 s.
Factory settings:
6 s
Display
source n
read/
write
For selecting the value to be displayed. Possible settings:
• Off
• Primary Value 1
• Sensor Value 1
• Primary Value 2
• Sensor Value 2
• RJ Value
Factory settings:
Primary Value 1
! Note!
If all 3 display channels are switched off ('Off' option), the
value for primary value 1 automatically appears on the dis-
play. If this value is not available (e.g. 'No Sensor' option
selected in the Sensor Transducer Block 1 parameter
'Characterization type 1'), primary value 2 is displayed.
Display value
description n
read/
write
Description of the display value displayed.
Factory settings:
"P1 "
! Note!
Maximum 16 letters. The value is not shown on the dis-
play.