Levelflex FMP51 Modbus
22 Endress+Hauser
-80 (-3.15)
-100 (-3.94)
-120 (-4.72)
-60 (-2.36)
-40 (-1.57)
-20 (-0.79)
0
20 (0.79)
40 (1.57)
60 (2.36)
80 (3.15)
100 (3.94)
120 (4.72)
DC = 2
DC = 80
30 (0.79)
A
D
0
50 (1.97)
100 (3.94)
150 (5.91)
200 (7.87)
250 (9.84)
300 (11.8)
A0021483
 6 Measuring error at the end-of-probe for probes with metallic centering disk (product structure: feature
610 "Accessory mounted", option OA, OB or OC)
A Distance from probe end [mm(in)]
D Measuring error: Sum of non-linearity, non-repeatability and hysteresis
If for rope probes the DC value is less than 7, then measurement is not possible in the area of
the straining weight (0 to 250 mm from end of probe; lower blocking distance).