Installation at an angle
A0014145
• For mechanical reasons, the probe should be installed as vertically as possible.
• With inclined installations the probe length has to be adjusted in dependence to the installation
angle.
– Up to LN = 1 m (3.3 ft): α = 30°
– Up to LN = 2 m (6.6 ft): α = 10°
– Up to LN = 4 m (13.1 ft): α = 5°