Levelflex FMP55 HART Commissioning (via operating menu)
Endress+Hauser 45
7. Setup → Empty calibration
Enter the distance E between the reference point R and the minimum level (0%).
8. Setup → Full calibration
Enter distance F between the minimum (0%) and maximum (100%) level.
9. Setup → Level
Displays the measured level L
L
.
10. Setup → Interface
Displays the interface height L
I
.
11. Setup → Distance
Displays the distance D
L
between the reference point R and the level L
L
.
12. Setup → Interface distance
Displays the distance D
I
between the reference point R and the interface L
I
.
13. Setup → Signal quality
Displays the signal quality of the level echo.
14. Setup → Mapping → Confirm distance
Make sure the vessel is completely empty. Then select the Tank empty option.
NOTICE
Wrong dielectric constant of the lower medium may cause a measuring error.
‣
If in the case of Operating mode = Interface with capacitance the lower medium is no
water, it is necessary to specify its dielectric constant (DC value): Setup → Advanced setup
→ Interface → DC value lower medium
NOTICE
Wrong empty capacity may cause a measuring error.
‣
For rod and rope probes with Operating mode = Interface with capacitance, a correct
measurement is only possible after the empty capacity has been determined. To do so,
make sure that the vessel is completely empty. Then select Confirm distance = Tank
empty (Step 13 in the table above).
For coax probes the correct empty capacitance is always set on delivery.
9.6 User-specific applications
For details of setting the parameters of user-specific applications, see separate
documentation:
BA01003F (Operating Instructions FMP55, HART)
For the Expert submenu refer to:
GP01000F (Description of Device Parameters FMP5x, HART)