Operating menu Levelflex FMP55 HART
112 Endress+Hauser
Selection SI units
• mm
• m
US units
• ft
• in
Factory setting m
Tank type
Navigation Setup → Tank type
Prerequisite Medium type = Liquid
Description Select tank type.
Selection • Metallic
• Bypass / pipe
• Non metallic
• Mounted outside
• Coaxial
Factory setting Depending on the probe
Additional information • Depending on the probe some of the options mentioned above may not be available or
there may be additional options.
• For coax probes, the default setting is Tank type = Coaxial and can not be changed.
• For probes with metallic center washer, Tank type = Bypass / pipe is preset and can not
be changed.
Tube diameter
Navigation Setup → Tube diameter
Prerequisite • Tank type (→ 112) = Bypass / pipe
• The probe is coated.
Description Specify diameter of bypass or stilling well.
User entry 0 to 9.999 m
Factory setting 0.0384 m