Operating menu Levelflex FMP55 HART
140 Endress+Hauser
Level (Manual)
Navigation Setup → Advanced setup → Linearization → Level
Prerequisite • Linearization type (→ 134) = Table
• Table mode (→ 138) = Manual
Description Enter level value of the table point (value before linearization).
User entry Signed floating-point number
Factory setting 0 %
Level (Semiautomatic)
Navigation Setup → Advanced setup → Linearization → Level
Prerequisite • Linearization type (→ 134) = Table
• Table mode (→ 138) = Semiautomatic
Description Displays measured level (value before linearization). This value is transmitted to the table.
Customer value
Navigation Setup → Advanced setup → Linearization → Customer value
Prerequisite Linearization type (→ 134) = Table
Description Enter linearized value for the table point.
User entry Signed floating-point number
Factory setting 0 %
Activate table
Navigation Setup → Advanced setup → Linearization → Activate table
Prerequisite Linearization type (→ 134) = Table
Description Activate (enable) or deactivate (disable) the linearization table.
Selection • Disable
• Enable