Levelflex FMP55 HART Operating menu
Endress+Hauser 187
Description of parameters
Navigation  Expert → Diagnostics → Simulation
Assign measurement variable
Navigation  Expert → Diagnostics → Simulation → Assign meas.var.
Description Selct process variable to be simulated.
Selection Off
Level
Interface
*
Thickness upper layer
*
Level linearized
Interface linearized
Thickness linearized
Factory setting Off
Additional information The value of the variable to be simulated is defined in the Process variable value
parameter (→  187).
If Assign measurement variableOff, a simulation is active. This is indicated by a
diagnotic message of the Function check (C) category.
Process variable value
Navigation  Expert → Diagnostics → Simulation → Proc. var. value
Prerequisite Assign measurement variable (→  187)Off
Description Specify value of the process value being simulated.
User entry Signed floating-point number
Factory setting 0
Additional information Downstream measured value processing and the signal output use this simulation value. In
this way, users can verify whether the measuring device has been configured correctly.