Technical data Levelflex M FMP40 FOUNDATION Fieldbus
102 Endress+Hauser
10.1.4 Performance characteristics
Reference operating
conditions
temperature = +20 °C ±5 °C
pressure = 1013 mbar abs. ±20 mbar
humidity = 65 % ±20 %
Reflection factor 0.8 (surface of the water for coax probe, metal plate for rod and rope probe
with min. 1 m )
Flange for rod or rope probe 30 cm
Distance to obstructions 1m
Maximum measured error Is in Function group "basic setup".
Resolution Digital: 1 mm
Reaction time The reaction time is dependent on the configuration.
Shortest time:
2-wire electronics: 1 s
Influence of ambiente
temperature
The measurements are carried out in accordance with EN 61298-3:
digital output:
average T
K
: 0.6 mm/10 K, max. ±3.5 mm over the entire temperature range -40 °C to +80 °C