Liquicap M FMI51 HART Commissioning
Endress+Hauser 59
4 mA
0 %
20 mA
100 %
H
B
C
A0040554
H The intermediate height
B The maximum tank content
C Customer unit
The following parameters must be specified:
the unit for the linearized value
The intermediate height in accordance with the diagram
the maximum tank contents measured in a customer unit
Options:
Table
In this type of linearization, the measured value is calculated using a linearization table.
The table can comprise up to 32 "Level - Volume" value pairs. The table must be monotone.
4 mA
0 %
20 mA
100 %
A0040562
The following parameters must be specified:
the unit for the linearized value
the linearization table
Subfunction: "Mode"
In this subfunction, specify whether the measurement should refer to level A or to the
empty area B.