Diagnostics and troubleshooting Liquicap M FMI51 HART
76 Endress+Hauser
8 Diagnostics and troubleshooting
The operating status of the device is indicated by the LEDs on the electronic insert.
8.1 Diagnostic information via LEDs
8.1.1 Green LED flashing
Green LED indicates operation:
flashes every 5 s
the device is in the operation mode
flashes once per 1 s
the device is in the calibration mode
flashes 4x:
the device confirms a parameter change, function switch position 4, 5, 6
8.1.2 Red LED flashing
To analyze the errors find the list in the chapter "Error codes" →  77
Red LED indicates a fault.
Warning: LED flashes 5x per second
capacitance at probe is too high
probe insulation break detection
FEI50H is defective
Alarm: LED flashes 1x per second
the temperature in the electronic insert is over the permitted range
8.2 System error messages
8.2.1 Error signal
Errors occurring during commissioning or during operation are displayed as follows:
error symbol, error code and error description on the display and operating module
current output, can be set:
Max: 110%, 22 mA
Hold - last value is retained
User-spec. value
8.2.2 Last errors
This function enables to call up a list of most recent errors.
8.2.3 Types of error
The alarm is represented by the symbol
which appears on the display. An error message
is also shown on the display.
The output signal assumes a value that can be specified with the "Output on alarm"
function:
Max: 110%, 22 mA
Hold - last value is retained
User-spec. value