Liquiline CM442R/CM444R/CM448R Diagnostics and troubleshooting
Endress+Hauser 123
11.9 Event logbook
11.9.1 Available logbooks
Types of logbooks
• Logbooks physically available (all apart from the overall logbook)
• Database view of all logbooks (=overall logbook)
11.9.2 Logbooks menu
Logbook Visible in Max.
entries
Can be
disabled
1)
1) Data in brackets means this depends on the overall logbook
Logbook
can be
deleted
Entries
can be
deleted
Can be
exported
Overall logbook All events 1000 Yes No Yes No
Calibration logbook Calibration events 75 (Yes) No Yes Yes
Operation logbook Configuration events 250 (Yes) No Yes Yes
Diagnostics logbook Diagnostic events 250 (Yes) No Yes Yes
Version logbook All events 50 No No No Yes
Hardware version
logbook
All events 125 No No No Yes
Data logbook for sensors
(optional)
Data logbooks 150,000 Yes Yes Yes Yes
Debugging logbook Only accessible with the
special activation code
(Service)
1000 Yes No Yes Yes
Diagnostics/Logbooks
Function Options Info
All events Chronological list of all the logbook entries, with
information on the type of event.
Show Events are displayed Select a particular event to display more detailed
information.
Go to date User input
• Go to date
•Time
Use this function to go directly to a specific time in the
list. In this way, you avoid having to scroll through all
the information. The complete list is always visible,
however.
Calibration events Chronological list of the calibration events.
Show Events are displayed Select a particular event to display more detailed
information.