Endress+Hauser 141
No. Message Factory settings Tests or remedial action
S
1)
D
2)
F
3)
436 SD card (80%) M On Off SD card 80% full
1. Replace SD card with empty card.
2. Clear SD card.
3. Set logbook properties to circular buffer
(Setup/General settings/Logbooks).
437 SD card (100%) M On Off SD card 100% full. No longer possible to write to
the card.
1. Replace SD card with empty card.
2. Clear SD card.
3. Set logbook properties to circular buffer
(Setup/General settings/Logbooks).
438 SD card removed M On Off SD card not plugged in
1. Check SD card.
2. Replace SD card.
3. Disable logging.
455 Mathemat. function F On On Mathematical function: fault condition
1. Check mathematical function.
2. Check assigned input variables.
460 Output below limit S On Off Reasons
Sensor in air
Air pockets in assembly
Sensor fouled
Incorrect flow to sensor
1. Check sensor installation.
2. Clean sensor.
3. Change assignment of current outputs.
461 Output above limit S On Off
502 No text catalog F On On
Contact the Service Department.
503 Language change M On Off Language change failed
Contact the Service Department.
529 Diag. setup active C Off Off
Wait for maintenance to be finished.
530 Logbook at 80% M On Off 1. Save the logbook to the SD card and then
delete the logbook in the device.
2. Set memory to circular buffer.
3. Deactivate logbook.
531 Logbook full M On Off
532 License error M On Off
Contact the Service Department.
540 Parameter save fail M On Off Storage of configuration has failed
Repeat.
541 Parameter load ok M On Off Configuration successfully loaded
542 Parameter load fail M On Off Loading of configuration has failed
Repeat.
543 Parameter load abort M On Off Configuration loading aborted
544 Parameter reset ok M On Off Factory default successful
545 Parameter reset fail M On Off Setting of device configuration to factory setting
has failed