Liquiphant FTL64
8 Endress+Hauser
Behavior of switch output
and signaling
MAX
RD YE GN
MIN
K
K
K
K
K
(N)
(N)
(N)
(N)
(N)
I
L
I
L
<3.8 mA
<3.8 mA
<3.8 mA
2
2
2
2
2
1
1
1
1
1
L1
L1
L1
L1
L1
ΔU
ΔU
A0031901
3 Behavior of switch output and signaling, electronic insert FEL61
MAXDIP switch for setting MAX safety mode
MIN DIP switch for setting MIN safety mode
RD LED red for warning or alarm
YE LED yellow, switch status
GN LED green, operational status, device on
I
L
Load current switched through
Selection tool for relays
3.0
1.5
1.3
20 24 27 43 48 53 60 110 121 207 230 253
S
U
P1
A0042052
4 Recommended minimum holding power/rated power for load
S Holding power/rated power in [VA]
U Operating voltage in [V]
AC mode
• Operating voltage: 24 V, 50 Hz/60 Hz
• Holding power/rated power: > 0.5 VA, < 8.4 VA
• Operating voltage: 110 V, 50 Hz/60 Hz
• Holding power/rated power: > 1.1 VA, < 38.5 VA
• Operating voltage: 230 V, 50 Hz/60 Hz
• Holding power/rated power: > 2.3 VA, < 80.5 VA