Liquiphant M FTL50(H), FTL51(H)
Endress+Hauser 33
Version NAMUR and DC-PNP with M12x1 round connector 316L
L00-FTL5xxxx-07-05-xx-xx-003
Green light (gn) lights up (DC-PNP):
Liquiphant M is connected to the power supply and is operational.
Green light (gn) flashing with 1 Hz (NAMUR):
Liquiphant M is connected to the power supply and is operational.
Yellow light (ye) lights up (DC-PNP):
Sensor is immersed in liquid.
Yellow light (ye) lights up (NAMUR):
MAX application mode (overfill protection): sensor is not immersed in liquid.
MIN application mode (dry running protection): sensor is immersed in liquid.
Red light (rd) flashing (DC-PNP):
Liquiphant M has detected a fault.
Green light (gn) flashing with 0.3 Hz (NAMUR):
Liquiphant M has detected a fault.