Liquistation CSF34 Operation
Endress+Hauser 115
Menu/Setup/Inputs
Function Options Info
Interval Selection
Daily
Weekly
Monthly
Factory setting
Daily
Daily
If a daily interval is selected, set the Time in
the following menu item.
Weekly
If a weekly interval is selected, set the Day
of week and the Time in the following
menu items.
Monthly
If a monthly interval is selected, set the Day
of month and the Time in the following
menu items.
Time 00:00:00 ... 23:59:59
HH:MM:SS
Factory setting
12:00:00 HH:MM:SS
Input variable External event
Signal slope Selection
Low-High; High
High-Low; Low
Factory setting
Low-High; High
A signal slope or a signal state triggers the
function assigned to the binary input. The
choice between signal slope and signal state
is performed automatically by the function
assigned to the binary input.
If Input variable Armature end position detection is selected (only for version with sampling assembly)
Position Selection
Off
Front (sampling)
Back (dosing)
Factory setting
Off
Setting specifying the assembly position
(front or back) to which the end position
sensor is connected.
Binary input assignment view Overview of the outputs to which this binary
input is linked.
10.4.2 Current inputs
The current input must be assigned an analog signal for the functions described. Active
and passive current inputs are available to connect two-wire or four-wire devices.
For the correct wiring of the current inputs see the "Electrical connection" section →  23
Menu/Setup/Inputs
Function Options Info
Current input S:x
Mode Selection
Off
0..20 mA
4..20 mA
Factory setting
Off
Enter the output signal of the connected
device: 0 to 20 mA or 4 to 20 mA.

Table of Contents