Loading...
Inputs: Interface Liquistation CSF48
178
18.3 Tank configuration
The mounting location is defined by the tank depth and the sensor zero point. The accuracy of
the measurement results depends on the accuracy of these settings.
Since the data in the sensor are overwritten with each change, data input might be delayed.
Path: Menu/Setup/Inputs/Ultrasonic interface/Tank configuration
Function Options Info
Blanket definition Options
•Interface level
Interface range
Factory setting
Interface level
Type of measurement that should be displayed and
calculated:
Interface level
Distance from the tank floor to the interface, measuring
direction from bottom to top
Interface range
Distance from the water line to the interface, measuring
direction from top to bottom
Unit of measure Options
•m
•cm
•ft
•inch
Factory setting
m
Any change to the unit is automatically accepted in all
the displays.
Tank depth 0.4 to 10.0 m (1.4 to 32.8
ft)
Factory setting
8.0 m (26.2 ft)
Distance from the water level to the tank floor
Zero adjust 0.4 to 10.0 m (1.4 to 32.8
ft)
Factory setting
0.4 m (1.3 ft)
Distance from the water level to the sensor diaphragm
Blanking zone Options
•Off
•On
Factory setting
Off
Permanent echo signals above and below a search
window are masked out as interference signals.
Upper window limit 0.0 m to Lower window limit
(1.4 ft ...)
Factory setting
0.3 m (1.0 ft)
Distance to the water line below which the system
should search for an interface.
Permanent echo signals above this value are masked
out as interference signals.
Lower window limit Upper window limit to
11.0 m (to 32.8 ft)
Factory setting
3.3 m (10.8 ft)
Distance to the water line
Permanent echo signals below this value are masked
out as interference signals.