Programming Liquistation CSF48
50
Settings with the Basic program type with multiple bottles
Sampling mode = "Time/flow paced CTVV"
Start time 00:00:00 to 23:59:59
Factory setting
HH:MM:SS (24h)
Set the time when the sampling program is started.
The format depends on the option configured under
general settings.
Stop condition Options
•Program end
Continuous
Factory setting
Program end
Program end:
The device stops sampling automatically once it has
run through the set program.
Continuous:
The device runs through the set program
continuously in an infinite loop. Do not forget to
empty the bottles.
Assignment bin. output Options
No binary output config. for
state reporting
Binary output S:x
Factory setting
No binary output config. for
state reporting
Assignment of the binary output to the program
cycle.
Inputs Settings for the inputs can be made as
described in the "Inputs" section.
Path: Menu/Setup/Sampling programs/Setup program/New/Basic
Function Options Info
Sampling volume input Options
No flow input configured
Binary input S:x
Current input S:x
Factory setting
No flow input configured
Select the sampling volume input.
The binary input or the current input must be
configured for this function.
Only the inputs configured as a sampling volume
input are displayed.
Sampling interval 00:01:00 to 99:59:00
HH:MM:SS
Factory setting
00:10:00 HH:MM:SS
Set the sampling interval.
If Sampling volume input Binary input is selected:
Sampling volume / pulse 10 to 1000 ml
Factory setting
20 ml
Set what sampling volume should be grabbed per
pulse.
The dosing accuracy and the repeatability of a
sample volume < 20 ml can vary, depending on
the specific application.
Path: Menu/Setup/Sampling programs/Setup program/New/Basic