First enter the desired current output configuration into the following blank table with a
pencil. Calculate the resulting signal distance per mA to observe the necessary minimum
slope. Then enter the values in the device.
Current output 1 Current output 2
Value pair .....[] Current
[mA]
Distance
per mA
.....[] Current
[mA]
Distance
per mA
1
2
3
4
5
6
7
8
9
10
Functions marked in italics are not supported by the basic device version.
Coding Field Range of
adjustment
(factory settings
in bold)
Display Info
O
CURRENT
OUTPUT
function group
A0025026-EN
Configuration of the current
output (does not apply for
PROFIBUS).
O1 Select current
output
Out 1
Out 2
A0025027-EN
A characteristic can be selected
for every output.
O2 Select measured
variable for 2nd
current output
°C
Contr
A0025028-EN
pH or ORPmV only with EP
version and depending on
option selected in B1. R247 or
R257 =curr (current output 2)
can only be selected if
O2=Contr (controller output) is
selected.
O3 (1) Enter the
characteristic
type
Lin = linear (1)
Sim = simulation
(2)
Tab = table (3)
A0025029-EN
The characteristic can have a
positive or negative slope for
the measured value output.
In the case of actuating
variable output (O2 = Contr),
an increasing current
corresponds to an increasing
actuating variable.