Commissioning Liquisys M CUM223/253
50 Endress+Hauser
Control and fine optimization of the set parameters with a recorder
Actuating signal outputs (R237 to R2310)
Each control contact outputs a cyclical signal whose intensity corresponds to the controller's
manipulated variable. A distinction is made according to the type of signal cycle:
Pulse length modulation
The bigger the calculated manipulated variable is, the longer the contact affected remains
picked up. The period T can be adjusted between 0.5 and 99 s (field R238). Outputs with
pulse length modulation are used to activate solenoid valves.
Pulse frequency modulation
The bigger the calculated manipulated variable is, the higher the switching frequency of
the contact affected. The maximum switching frequency 1/T can be set between 60 and
180 min
-1
. The on-time t
ON
is constant. It depends on the set maximum frequency and is
approx. 0.5 s for 60 min
-1
and approx. 170 ms for 180 min
-1
. Outputs with pulse frequency
modulation are used to activate directly controlled solenoid dosing pumps.
a0008924
Optimization of settings T
n
and K
p
A
B
Actual value
Time
1
2
3
T
n
too small
T
n
too large
K
p
too large
4
5
K
p
too small
Optimum setting
a0008928
Fig. 27: Signal of a pulse-length modulated controller contact (left) and of a pulse-frequency modulated controller contact (right)
A
B
Contact 1 = on, 0 = off
Time [s] t
1
= t
on
t
2
= t
off
T
T
1
T
2
Period length
Impulse period length (impulse freq. 1/T
1
and 1/
T
2
)
A
B
A
B
A
B
A
B
A
B
1
2
3
4
5
A
1
0
T
t [s]
A
t [s]
t
1
t
2
t
1
1
0
T
1
T
2