Installation Micropilot FMR50 HART
14 Endress+Hauser
6 Installation
6.1 Installation conditions
6.1.1 Mounting position
A0016882
• Recommended distance A from wall
to outer edge of nozzle: ~ 1/6 of tank
diameter.
Nevertheless the device should not be
installed closer than 15 cm (5.91 in)
to the tank wall.
• Not in the center (2), as interference
can cause signal loss.
• Not above the fill stream (3).
• It is recommended to us a weather
protection cover (1) in order to protect
the device from direct sun or rain.