EasyManua.ls Logo

Endress+Hauser Micropilot FMR50 - Page 43

Endress+Hauser Micropilot FMR50
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Micropilot FMR50 HART Electrical connection
Endress+Hauser 43
"Power
Supply,
Output"
1)
"Approval"
2)
Terminal
voltage U at
the device
Maximum load R, depending on the supply voltage U
0
at the supply
unit
B: 2-wire;
4-20 mA
HART,
switch
output
Non-Ex
Ex nA
Ex nA(ia)
Ex ic
Ex ic(ia)
Ex d(ia) /
XP
Ex ta / DIP
CSA GP
13 to 35 V
3) 4)
U
0
[V]
10
13 24
20 30 35
0
500
R [ ]Ω
A0034771
Ex ia / IS
Ex ia + Ex
d(ia) / IS +
XP
13 to 30 V
3) 4)
1) Feature 020 of the product structure
2) Feature 010 of the product structure
3) For ambient temperatures T
a
≤ -30 °C (-22 °F) a minimum voltage of 16 V is required for the startup of the device
at the minimum error current (3.6 mA).
4) If the Bluetooth modem is used, the minimum supply voltage increases by 3 V.
"Power
Supply,
Output"
1)
"Approval"
2)
Terminal
voltage U at
the device
Maximum load R, depending on the supply voltage U
0
at the
supply unit
C: 2-wire;
4-20mA
HART,
4-20mA
any 13 to 28 V
3) 4)
R [ ]W
U
0
[V]
10
13 24
20 28
0
500
A0034841
1) Feature 020 of the product structure
2) Feature 010 of the product structure
3) For ambient temperatures T
a
≤ -30 °C (-22 °F) a minimum voltage of 16 V is required for the startup of the device
at the minimum error current (3.6 mA).
4) If the Bluetooth modem is used, the minimum supply voltage increases by 3 V.

Other manuals for Endress+Hauser Micropilot FMR50

Related product manuals